Load Calculation of Psychrometry Question 1:

In a theatre, heat is generated at the rate of 150 kJ/s due to the occupants, music and display system and other lighting. The rate of generation of excess moisture is 45 kg/hr. The theatre is provided with an air conditioner that is supplying conditioning at 600 m3/min. Calculate the Sensible heat factor for the theatre.

Answer (Detailed Solution Below) 0.81 - 0.83

Load Calculation of Psychrometry Question 1 Detailed Solution

Concept:

Sensible heat factor is defined as the ratio of sensible heat to total heat. Sensible heat is defined as the heat that causes a change in temperature and latent heat is the one that causes a change in phase and cannot be sensed. Total heat is the sum of sensible heat and latent heat.

 

Calculation:

Sensible heat = 150 kJ/s

Latent heat =

Total heat = SH + LH = 181.25 kJ/s

SHF = 150/181.25 = 0.83

Load Calculation of Psychrometry Question 2:

Air entering the cooling coil 20% RH and 80% recirculating air. The outside air has enthalpy of 85 kJ/kg of da, and the room air has hi = 50.8 kJ/kg of da and the mixture has h1 = 57.64 kJ/kg of da. The air enthalpy corresponding to cooling coil temperature hs = 37.0 kJ/kg of da. The ratio of total cooling load to fresh air load is

Answer (Detailed Solution Below) 3.0 - 3.1

Load Calculation of Psychrometry Question 2 Detailed Solution

Total cooling load = h1 – hs = 57.64 – 37 = 20.64 kJ/kg of da

Fresh air load = 0.2 (85 – 50.8) = 6.84 kJ/kg of da

Load Calculation of Psychrometry Question 3:

40  of air of sp.humidity 8.2 gm/kg of air, enthalpy 52.5 kJ/kg and sp.volume 0.87 m3/kg is passed over a cooling coil. Cooling coil capacity is 3.5 tonne of refrigeration, enthalpy 17.7 kJ/kg and sp.humidity 5.25 gm/kg. what will be sp.humidity of air leaving cooling coil ?

  1. 4.88 gm/kg of air 

  2. 6.85 gm/kg of air 

  3. 5.11 gm/kg of air 

  4. 9.33 gm/kg of air 

Answer (Detailed Solution Below)

Option 2 :

6.85 gm/kg of air 

Load Calculation of Psychrometry Question 3 Detailed Solution

Tonne of refrigeration 

Sensible heat factor for cooling and dehumidification 

∴ w2 = 6.85 gm/kg of air 