A three phase breaker is rated at 2000 MVA, 33 kV, its making current is

This question was previously asked in
JKSSB JE Electrical 2015 Official Paper
View all JKSSB JE Papers >
  1. 70 kA
  2. 89 kA
  3. 49 kA
  4. 35 kA  

Answer (Detailed Solution Below)

Option 2 : 89 kA
Free
JKSSB JE Civil RCC Structures Mock Test
1 K Users
20 Questions 20 Marks 20 Mins

Detailed Solution

Download Solution PDF

Explanation:

Three-Phase Breaker Making Current

Problem Statement: A three-phase breaker is rated at 2000 MVA and 33 kV. The task is to calculate its making current.

Solution:

To calculate the making current of the three-phase breaker, we use the standard formula:

Making Current = √2 × Symmetrical Breaking Current

The symmetrical breaking current can be determined using the formula:

Symmetrical Breaking Current (Isym) = Rated MVA / (√3 × Rated Voltage)

Given data:

  • Rated MVA (S) = 2000 MVA
  • Rated Voltage (V) = 33 kV = 33 × 103 V

Step 1: Calculate the symmetrical breaking current:

Isym = S / (√3 × V)

Substituting the values:

Isym = 2000 × 106 / (√3 × 33 × 103)

We know that √3 ≈ 1.732, so:

Isym = 2000 × 106 / (1.732 × 33 × 103)

Isym = 2000 × 106 / 57.156 × 103

Isym = 35,000 A or 35 kA

Step 2: Calculate the making current:

Making Current = √2 × Isym

We know that √2 ≈ 1.414, so:

Making Current = 1.414 × 35 kA

Making Current = 49.49 kA

Since the making current is typically rounded off to the nearest whole number, the making current is approximately 49 kA.

Correct Answer: Option 3) 49 kA

Important Information

To analyze the other options, let us evaluate them:

Option 1: 70 kA

This value is significantly higher than the calculated making current of 49 kA. A making current of 70 kA would correspond to a much higher symmetrical breaking current or a different breaker rating.

Option 2: 89 kA

This value is even higher than option 1 and is unrealistic for the given breaker ratings. A making current of 89 kA would require a symmetrical breaking current of over 63 kA, which does not match the given MVA and voltage ratings.

Option 4: 35 kA

This value represents the symmetrical breaking current, not the making current. The making current is always higher than the symmetrical breaking current due to the factor of √2.

Option 5: Not Provided

This option is irrelevant as it does not present any numerical value for consideration.

Conclusion:

The making current of the given three-phase breaker is accurately calculated to be approximately 49 kA, as derived from the rated MVA and voltage. Understanding the relationship between the symmetrical breaking current and the making current is crucial for accurately determining the breaker specifications and ensuring proper system protection.

Latest JKSSB JE Updates

Last updated on Jul 1, 2025

-> JKSSB Junior Engineer recruitment exam date 2025 for Civil and Electrical Engineering has been rescheduled on its official website. 

-> JKSSB JE exam will be conducted on 31st August (Civil), and on 24th August 2025 (Electrical).

-> JKSSB JE application form correction facility has been started. Candidates can make corrections in the JKSSB recruitment 2025 form from June 23 to 27. 

-> JKSSB JE recruitment 2025 notification has been released for Civil Engineering. 

-> A total of 508 vacancies has been announced for JKSSB JE Civil Engineering recruitment 2025. 

-> JKSSB JE Online Application form will be activated from 18th May 2025 to 16th June 2025 

-> Candidates who are preparing for the exam can access the JKSSB JE syllabus PDF from official website of JKSSB.

-> The candidates can check the JKSSB JE Previous Year Papers to understand the difficulty level of the exam.

-> Candidates also attempt the JKSSB JE Mock Test which gives you an experience of the actual exam.

Get Free Access Now
Hot Links: teen patti comfun card online teen patti star login happy teen patti teen patti master 2025