Line To Line To Ground Fault MCQ Quiz - Objective Question with Answer for Line To Line To Ground Fault - Download Free PDF
Last updated on Jun 11, 2025
Latest Line To Line To Ground Fault MCQ Objective Questions
Line To Line To Ground Fault Question 1:
A 30 MVA, 13.2 KV synchronous generator has a solidly grounded neutral. Its positive, negative and zero sequence impedances are 0.30, 0.40 and 0.05 pu respectively. What value of reactance must be placed in the generator neutral so that the fault current for a line to ground fault of zero fault impedance shall not exceed the rated line current.
Answer (Detailed Solution Below)
Line To Line To Ground Fault Question 1 Detailed Solution
Problem Statement: A 30 MVA, 13.2 KV synchronous generator has a solidly grounded neutral. Its positive, negative, and zero sequence impedances are 0.30 pu, 0.40 pu, and 0.05 pu respectively. We need to determine the value of reactance that must be placed in the generator neutral so that the fault current for a line-to-ground fault of zero fault impedance does not exceed the rated line current.
Solution:
To solve this problem, we will calculate the required reactance step by step:
Step 1: Determine the base current
The base current for the system can be calculated using the formula:
Ibase = (Sbase × 106) / (√3 × Vbase)
Here:
- Sbase = 30 MVA = 30 × 106 VA
- Vbase = 13.2 kV = 13.2 × 103 V
Substituting the values:
Ibase = (30 × 106) / (√3 × 13.2 × 103)
Ibase = 1311.78 A
So, the base current of the system is 1311.78 A.
Step 2: Determine the per unit fault current for a line-to-ground fault
In the case of a line-to-ground fault, the equivalent impedance is given by:
ZLG = Z1 + Z2 + (Z0 || ZN)
Where:
- Z1 = Positive sequence impedance = 0.30 pu
- Z2 = Negative sequence impedance = 0.40 pu
- Z0 = Zero sequence impedance = 0.05 pu
- ZN = Neutral reactance to be determined
The fault current is inversely proportional to the equivalent impedance. The fault current in per unit (If) for a line-to-ground fault can be expressed as:
If = 1 / ZLG
We are tasked with limiting the fault current to the rated line current (i.e., 1 pu). Hence, the equivalent impedance must satisfy:
ZLG = 1 pu
Substituting the values into the equation for ZLG:
1 = 0.30 + 0.40 + (0.05 || ZN)
Step 3: Solve for ZN
The parallel combination of Z0 and ZN is given by:
(0.05 || ZN) = (Z0 × ZN) / (Z0 + ZN)
Substituting this into the equation for ZLG:
1 = 0.30 + 0.40 + [(0.05 × ZN) / (0.05 + ZN)]
Rearranging:
0.30 + 0.40 = 0.70
1 - 0.70 = (0.05 × ZN) / (0.05 + ZN)
0.30 = (0.05 × ZN) / (0.05 + ZN)
Cross-multiplying:
0.30 × (0.05 + ZN) = 0.05 × ZN
Expanding and simplifying:
0.015 + 0.30 × ZN = 0.05 × ZN
0.30 × ZN - 0.05 × ZN = 0.015
0.25 × ZN = 0.015
Solving for ZN:
ZN = 0.015 / 0.25 = 0.06 pu
Step 4: Convert ZN to ohms
To convert the per unit reactance into ohms, we use the base impedance:
Zbase = (Vbase)2 / Sbase
Substituting the values:
Zbase = (13.2 × 103)2 / (30 × 106)
Zbase = 5.808 ohms
Now, the neutral reactance in ohms is:
XN = ZN × Zbase
XN = 0.06 × 5.808
XN = 0.34848 ohms
**Line To Line To Ground Fault Question 2:
Which fault is indicated in the given diagram?
Answer (Detailed Solution Below)
Line To Line To Ground Fault Question 2 Detailed Solution
The correct answer is option 4): (Double line to ground fault)
Concept:
A double-line-to-ground (DLG) fault is typically modeled as a short-circuit connection from two phases (i.e., Phases A and B) to a common point, with a fault resistance from the common point to the ground.
The two lines contact each other along with the ground. The probability of such types of faults is nearly 10 %.
All sequence networks are connected in parallel.
The given fault diagram is a Double line to ground fault
Ia0 + Ia1 + Ia2 = 0
Va0 = Va1 = Va2
IF = 3Ia0
Additional InformationThree Phase Line to Ground Fault:
The 3-phase to-ground faults are faults in which all the phases (A, B and C) are shorted together and they are grounded.
Three Phase Line to Line Fault:
The three-phase faults occur when having A, B and C phases are shorted together but the ground is not involved.
Line-to-ground fault:
A short circuit between one line and the ground, is very often caused by physical contact, for example, due to lightning or other storm damage. In transmission line faults, roughly 65% - 70% are asymmetric line-to-ground faults.
Line to line fault:
A line to line fault occurs when two conductors are short circuited
Line To Line To Ground Fault Question 3:
The reactance data for a power system is shown in the figure in per unit on a common base is as follows.
G1: X1 = X2 = j0.1, X0 = j0.05
G2: X1 = X2 = j0.1, X0 = j0.05
T1: X1 = X2 = j0.25, X0 = j0.25
T2: X1 = X2 = j0.25, X0 = j0.25
Line: X1 = X2 = j0.3, X0 = j0.5
If a double line to ground fault occurs at bus 1, the fault current is _______
Answer (Detailed Solution Below)
Line To Line To Ground Fault Question 3 Detailed Solution
For the given power system network, the positive sequence impedance network is given below.
The impedance at a point of fault is,
\({X_{1eq}} = \left( {j0.35} \right)\parallel \left( {j0.65} \right)\)
= j0.2275 pu
Negative sequence reactance is the same as positive sequence reactance
\({X_{2eq}} = {X_{1eq}} = j0.2275\;pu\)
The zero sequence reactance network is,
Zero sequence impedance
Z0eq = j0.25 ∥ j0.75 = j0.1875 pu
For a double line to fault at bus 1 is,
\({I_{a1}} = \frac{1}{{j0.2275 + j\frac{{\left( {0.2275} \right)\left( {0.1875} \right)}}{{0.2275 + 0.1875}}}} = - j3.02767\;pu\)
\({I_{a0}} = \frac{{1 - \left( {j0.2275} \right)\left( { - j3.02767} \right)}}{{j0.1875}} = j1.65975\;pu\)
If = 3Ia0 = j4.979 pu
Line To Line To Ground Fault Question 4:
A \(30\;MVA\), 3-phase, \(50\;Hz,\;13.8\;kV\), star-connected synchronous generator has positive, negative and zero sequence reactances, \(15\% ,\;15\% \;and\;5\%\) respectively. A reactance (\({X_n}\)) is connected between the neutral of the generator and ground. A double line to ground fault takes place involving phases \('b'\;and\;'c'\), with a fault impedance of \(j0.1\;p.u.\) The value of \({X_n}\) (in \(p.u.\)) that will limit the positive sequence generator current to \(4270\;A\) is _________.
Answer (Detailed Solution Below) 1.05 - 1.15
Line To Line To Ground Fault Question 4 Detailed Solution
We have the base current \({I_B} = \frac{{30 \times {{10}^3}}}{{\sqrt 3 \times 13.8}} = 1255.109\;A\)
The positive sequence current, \({I_p} = 4270\;A\)
Per unit current, \({I_{p.u.}} = \frac{{4270}}{{1255.109}} = 3.402\;p.u.\)
Fault impedance = 0.1 pu
Xn = 3zf + 0.05 + 3xn = 0.35 + 3xn
\(\begin{array}{l} {I_{g1}} = \frac{{{E_a}}}{{{X_1} + \left( {\left. {{X_2}} \right|} \right.\left| {\left. {{X_0}} \right)} \right.\;\;}}\\ {X_0}\; = \;3{X_n}\; + \;0.35\\ 3.402 = \frac{{1.0}}{{0.15 + \frac{{0.15 \times \left( {3{X_n} + 0.35} \right)}}{{0.15 + 3{X_n} + 0.35}}}} \end{array}\)
From above equation, we get \({X_n} = 1.07\;p.u\)Top Line To Line To Ground Fault MCQ Objective Questions
A \(30\;MVA\), 3-phase, \(50\;Hz,\;13.8\;kV\), star-connected synchronous generator has positive, negative and zero sequence reactances, \(15\% ,\;15\% \;and\;5\%\) respectively. A reactance (\({X_n}\)) is connected between the neutral of the generator and ground. A double line to ground fault takes place involving phases \('b'\;and\;'c'\), with a fault impedance of \(j0.1\;p.u.\) The value of \({X_n}\) (in \(p.u.\)) that will limit the positive sequence generator current to \(4270\;A\) is _________.
Answer (Detailed Solution Below) 1.05 - 1.15
Line To Line To Ground Fault Question 5 Detailed Solution
Download Solution PDFWe have the base current \({I_B} = \frac{{30 \times {{10}^3}}}{{\sqrt 3 \times 13.8}} = 1255.109\;A\)
The positive sequence current, \({I_p} = 4270\;A\)
Per unit current, \({I_{p.u.}} = \frac{{4270}}{{1255.109}} = 3.402\;p.u.\)
Fault impedance = 0.1 pu
Xn = 3zf + 0.05 + 3xn = 0.35 + 3xn
\(\begin{array}{l} {I_{g1}} = \frac{{{E_a}}}{{{X_1} + \left( {\left. {{X_2}} \right|} \right.\left| {\left. {{X_0}} \right)} \right.\;\;}}\\ {X_0}\; = \;3{X_n}\; + \;0.35\\ 3.402 = \frac{{1.0}}{{0.15 + \frac{{0.15 \times \left( {3{X_n} + 0.35} \right)}}{{0.15 + 3{X_n} + 0.35}}}} \end{array}\)
From above equation, we get \({X_n} = 1.07\;p.u\)Which fault is indicated in the given diagram?
Answer (Detailed Solution Below)
Line To Line To Ground Fault Question 6 Detailed Solution
Download Solution PDFThe correct answer is option 4): (Double line to ground fault)
Concept:
A double-line-to-ground (DLG) fault is typically modeled as a short-circuit connection from two phases (i.e., Phases A and B) to a common point, with a fault resistance from the common point to the ground.
The two lines contact each other along with the ground. The probability of such types of faults is nearly 10 %.
All sequence networks are connected in parallel.
The given fault diagram is a Double line to ground fault
Ia0 + Ia1 + Ia2 = 0
Va0 = Va1 = Va2
IF = 3Ia0
Additional InformationThree Phase Line to Ground Fault:
The 3-phase to-ground faults are faults in which all the phases (A, B and C) are shorted together and they are grounded.
Three Phase Line to Line Fault:
The three-phase faults occur when having A, B and C phases are shorted together but the ground is not involved.
Line-to-ground fault:
A short circuit between one line and the ground, is very often caused by physical contact, for example, due to lightning or other storm damage. In transmission line faults, roughly 65% - 70% are asymmetric line-to-ground faults.
Line to line fault:
A line to line fault occurs when two conductors are short circuited
A 30 MVA, 13.2 KV synchronous generator has a solidly grounded neutral. Its positive, negative and zero sequence impedances are 0.30, 0.40 and 0.05 pu respectively. What value of reactance must be placed in the generator neutral so that the fault current for a line to ground fault of zero fault impedance shall not exceed the rated line current.
Answer (Detailed Solution Below)
Line To Line To Ground Fault Question 7 Detailed Solution
Download Solution PDFProblem Statement: A 30 MVA, 13.2 KV synchronous generator has a solidly grounded neutral. Its positive, negative, and zero sequence impedances are 0.30 pu, 0.40 pu, and 0.05 pu respectively. We need to determine the value of reactance that must be placed in the generator neutral so that the fault current for a line-to-ground fault of zero fault impedance does not exceed the rated line current.
Solution:
To solve this problem, we will calculate the required reactance step by step:
Step 1: Determine the base current
The base current for the system can be calculated using the formula:
Ibase = (Sbase × 106) / (√3 × Vbase)
Here:
- Sbase = 30 MVA = 30 × 106 VA
- Vbase = 13.2 kV = 13.2 × 103 V
Substituting the values:
Ibase = (30 × 106) / (√3 × 13.2 × 103)
Ibase = 1311.78 A
So, the base current of the system is 1311.78 A.
Step 2: Determine the per unit fault current for a line-to-ground fault
In the case of a line-to-ground fault, the equivalent impedance is given by:
ZLG = Z1 + Z2 + (Z0 || ZN)
Where:
- Z1 = Positive sequence impedance = 0.30 pu
- Z2 = Negative sequence impedance = 0.40 pu
- Z0 = Zero sequence impedance = 0.05 pu
- ZN = Neutral reactance to be determined
The fault current is inversely proportional to the equivalent impedance. The fault current in per unit (If) for a line-to-ground fault can be expressed as:
If = 1 / ZLG
We are tasked with limiting the fault current to the rated line current (i.e., 1 pu). Hence, the equivalent impedance must satisfy:
ZLG = 1 pu
Substituting the values into the equation for ZLG:
1 = 0.30 + 0.40 + (0.05 || ZN)
Step 3: Solve for ZN
The parallel combination of Z0 and ZN is given by:
(0.05 || ZN) = (Z0 × ZN) / (Z0 + ZN)
Substituting this into the equation for ZLG:
1 = 0.30 + 0.40 + [(0.05 × ZN) / (0.05 + ZN)]
Rearranging:
0.30 + 0.40 = 0.70
1 - 0.70 = (0.05 × ZN) / (0.05 + ZN)
0.30 = (0.05 × ZN) / (0.05 + ZN)
Cross-multiplying:
0.30 × (0.05 + ZN) = 0.05 × ZN
Expanding and simplifying:
0.015 + 0.30 × ZN = 0.05 × ZN
0.30 × ZN - 0.05 × ZN = 0.015
0.25 × ZN = 0.015
Solving for ZN:
ZN = 0.015 / 0.25 = 0.06 pu
Step 4: Convert ZN to ohms
To convert the per unit reactance into ohms, we use the base impedance:
Zbase = (Vbase)2 / Sbase
Substituting the values:
Zbase = (13.2 × 103)2 / (30 × 106)
Zbase = 5.808 ohms
Now, the neutral reactance in ohms is:
XN = ZN × Zbase
XN = 0.06 × 5.808
XN = 0.34848 ohms
**Line To Line To Ground Fault Question 8:
A \(30\;MVA\), 3-phase, \(50\;Hz,\;13.8\;kV\), star-connected synchronous generator has positive, negative and zero sequence reactances, \(15\% ,\;15\% \;and\;5\%\) respectively. A reactance (\({X_n}\)) is connected between the neutral of the generator and ground. A double line to ground fault takes place involving phases \('b'\;and\;'c'\), with a fault impedance of \(j0.1\;p.u.\) The value of \({X_n}\) (in \(p.u.\)) that will limit the positive sequence generator current to \(4270\;A\) is _________.
Answer (Detailed Solution Below) 1.05 - 1.15
Line To Line To Ground Fault Question 8 Detailed Solution
We have the base current \({I_B} = \frac{{30 \times {{10}^3}}}{{\sqrt 3 \times 13.8}} = 1255.109\;A\)
The positive sequence current, \({I_p} = 4270\;A\)
Per unit current, \({I_{p.u.}} = \frac{{4270}}{{1255.109}} = 3.402\;p.u.\)
Fault impedance = 0.1 pu
Xn = 3zf + 0.05 + 3xn = 0.35 + 3xn
\(\begin{array}{l} {I_{g1}} = \frac{{{E_a}}}{{{X_1} + \left( {\left. {{X_2}} \right|} \right.\left| {\left. {{X_0}} \right)} \right.\;\;}}\\ {X_0}\; = \;3{X_n}\; + \;0.35\\ 3.402 = \frac{{1.0}}{{0.15 + \frac{{0.15 \times \left( {3{X_n} + 0.35} \right)}}{{0.15 + 3{X_n} + 0.35}}}} \end{array}\)
From above equation, we get \({X_n} = 1.07\;p.u\)Line To Line To Ground Fault Question 9:
Which fault is indicated in the given diagram?
Answer (Detailed Solution Below)
Line To Line To Ground Fault Question 9 Detailed Solution
The correct answer is option 4): (Double line to ground fault)
Concept:
A double-line-to-ground (DLG) fault is typically modeled as a short-circuit connection from two phases (i.e., Phases A and B) to a common point, with a fault resistance from the common point to the ground.
The two lines contact each other along with the ground. The probability of such types of faults is nearly 10 %.
All sequence networks are connected in parallel.
The given fault diagram is a Double line to ground fault
Ia0 + Ia1 + Ia2 = 0
Va0 = Va1 = Va2
IF = 3Ia0
Additional InformationThree Phase Line to Ground Fault:
The 3-phase to-ground faults are faults in which all the phases (A, B and C) are shorted together and they are grounded.
Three Phase Line to Line Fault:
The three-phase faults occur when having A, B and C phases are shorted together but the ground is not involved.
Line-to-ground fault:
A short circuit between one line and the ground, is very often caused by physical contact, for example, due to lightning or other storm damage. In transmission line faults, roughly 65% - 70% are asymmetric line-to-ground faults.
Line to line fault:
A line to line fault occurs when two conductors are short circuited
Line To Line To Ground Fault Question 10:
The reactance data for a power system is shown in the figure in per unit on a common base is as follows.
G1: X1 = X2 = j0.1, X0 = j0.05
G2: X1 = X2 = j0.1, X0 = j0.05
T1: X1 = X2 = j0.25, X0 = j0.25
T2: X1 = X2 = j0.25, X0 = j0.25
Line: X1 = X2 = j0.3, X0 = j0.5
If a double line to ground fault occurs at bus 1, the fault current is _______
Answer (Detailed Solution Below)
Line To Line To Ground Fault Question 10 Detailed Solution
For the given power system network, the positive sequence impedance network is given below.
The impedance at a point of fault is,
\({X_{1eq}} = \left( {j0.35} \right)\parallel \left( {j0.65} \right)\)
= j0.2275 pu
Negative sequence reactance is the same as positive sequence reactance
\({X_{2eq}} = {X_{1eq}} = j0.2275\;pu\)
The zero sequence reactance network is,
Zero sequence impedance
Z0eq = j0.25 ∥ j0.75 = j0.1875 pu
For a double line to fault at bus 1 is,
\({I_{a1}} = \frac{1}{{j0.2275 + j\frac{{\left( {0.2275} \right)\left( {0.1875} \right)}}{{0.2275 + 0.1875}}}} = - j3.02767\;pu\)
\({I_{a0}} = \frac{{1 - \left( {j0.2275} \right)\left( { - j3.02767} \right)}}{{j0.1875}} = j1.65975\;pu\)
If = 3Ia0 = j4.979 pu
Line To Line To Ground Fault Question 11:
A three-phase star-connected alternator rated at 30 MVA, 13.8 kV has positive, negative, and zero sequence reactance values as 0.25 pu, 0.35 pu, and 0.10 pu respectively. The neutral of the alternator is solidly grounded. Find the current in phase B when a double line to ground fault occurs on its terminals B and C.
Answer (Detailed Solution Below)
Line To Line To Ground Fault Question 11 Detailed Solution
The equivalent circuit for LLG fault can be drawn as:
Z1 = j0.25 pu, E = 1 pu
Z2 = j0.35 pu
Z0 = j0.10 pu
\({I_{{a_1}}} = \frac{E}{{{Z_1} + \left( {{Z_2}\parallel {Z_0}} \right)}} = \frac{1}{{j0.25 + \left( {j0.35\parallel j0.10} \right)}} = j3.05\;pu\)
\({I_{{a_0}}} = - \frac{{{Z_2}}}{{{Z_0} + {Z_2}}}{I_{{a_1}}} = - j2.372\;pu\)
Similarly \({I_{{a_2}}} = - \frac{{{Z_0}}}{{{Z_0} + {Z_2}}}{I_{{a_1}}} = - j0.677\;pu\)
We know that \(\left[ {\begin{array}{*{20}{c}} {{I_a}}\\ {{I_b}}\\ {{I_c}} \end{array}} \right] = \left[ {\begin{array}{*{20}{c}} 1&1&1\\ 1&{{\alpha ^2}}&\alpha \\ 1&\alpha &{{\alpha ^2}} \end{array}} \right]\left[ {\begin{array}{*{20}{c}} {{I_{{a_0}}}}\\ {{I_{{a_1}}}}\\ {{I_{{a_2}}}} \end{array}} \right]\)
\({I_b} = {I_{{a_0}}} + {\alpha ^2}{I_{{a_1}}} + \alpha {I_{{a_2}}}\)
α = 1∠120°
α2 = 1∠-120°
⇒ Ib = 4.804 pu
Line To Line To Ground Fault Question 12:
Determine the fault current in a system following a double line to ground short circuit at the terminals of a star connected synchronous generator operating initially on an open circuit voltage of 1.0 pu. The positive, negative and zero sequence reactance of the generator are, respectively j 0.35, j 0.25 and j 0.20 and the star point is isolated from ground.
Answer (Detailed Solution Below)
Line To Line To Ground Fault Question 12 Detailed Solution
Since the star point is isolated from ground LLG fault is just like LL fault.
\({I_b} = - {I_c} = \frac{{ - j\;\sqrt 3 \times 1}}{{j\;0.35 + j\;0.25}} = - 2.887\;pu\)
Line To Line To Ground Fault Question 13:
A 30 MVA, 13.2 KV synchronous generator has solid grounded neural. It positive, negative and zero sequence impedance are 0.30, 0.40 and 0.05 PU respectively. What value of reactance (in ohm) must be placed in the neutral of the generator to restrict the fault current to ground to rated line current for a double line to ground fault.
Answer (Detailed Solution Below) 2.7 - 3.2
Line To Line To Ground Fault Question 13 Detailed Solution
First find rated current of generator
\({I_g}rated\; = \frac{{30000}}{{\sqrt 3 \times 13.2}} = 1312.16\;AmP\)
Taking rated voltage and MVA as base
\(Base\;Impedance = \frac{{{{\left( {13.2} \right)}^2}}}{{30}} = 5.88\;{\rm{\Omega }}\)
Z1 = j0.30 PU, Z2 = J 0.40 PU Z0 = J 0
Double line to ground fault
IF = 3Ia0
\( = \frac{{ - 3{E_a}}}{{{Z_0} + 3{Z_f}}} + \frac{{{Z_1}}}{{{Z_0} + 3{Z_f}}}.\frac{{3{E_a}}}{{{Z_1} + \frac{{{Z_2}\left( {{Z_0} + 3{Z_f}} \right)}}{{\left( {{Z_2} + {Z_0} + 3{Z_f}} \right)}}}}\)
\({I_F} = \frac{{{E_a}}}{{{Z_0} + 3{Z_f}}}( - 1 + \frac{{{Z_1}\left( {{Z_2} + {Z_0} + 3{Z_f}} \right)}}{{{Z_1}\left( {{Z_2} + {Z_0} + {Z_f}} \right) + {Z_2}\left( {{Z_0} + 3{Z_f}} \right)}}\)
\({I_F} = \frac{{ - 3{Z_2}{E_a}}}{{{Z_1}\left( {{Z_2} + {Z_0} + 3{Z_f}} \right) + {Z_2}\left( {{Z_0} + 3{Z_f}} \right)}}\)
\({I_F} = \frac{{ - 3{Z_2}{E_a}}}{{{Z_1}{Z_2} + \left( {{Z_0} + 32F} \right)\left( {{Z_1} + {Z_2}} \right)}}\)
\(\therefore \left| {\frac{{3 \times 1 \times J\;0.4}}{{J\;0.3 \times J\;0.4 + J\;\left( {0.3 + 0.4} \right)\left( {J\;0.05 + J\;3{X_n}} \right)}}} \right| = 1\)
∴ 0.12 + 0.7 (0.05 + 3Xn) = 1.2
Xn = 0.5 PU = 0.5 × 5.88 = 2.94 Ω
Line To Line To Ground Fault Question 14:
A 30 MVA, 13.2 KV synchronous generator has a solidly grounded neutral. Its positive, negative and zero sequence impedances are 0.30, 0.40 and 0.05 pu respectively. What value of reactance must be placed in the generator neutral so that the fault current for a line to ground fault of zero fault impedance shall not exceed the rated line current.
Answer (Detailed Solution Below)
Line To Line To Ground Fault Question 14 Detailed Solution
Problem Statement: A 30 MVA, 13.2 KV synchronous generator has a solidly grounded neutral. Its positive, negative, and zero sequence impedances are 0.30 pu, 0.40 pu, and 0.05 pu respectively. We need to determine the value of reactance that must be placed in the generator neutral so that the fault current for a line-to-ground fault of zero fault impedance does not exceed the rated line current.
Solution:
To solve this problem, we will calculate the required reactance step by step:
Step 1: Determine the base current
The base current for the system can be calculated using the formula:
Ibase = (Sbase × 106) / (√3 × Vbase)
Here:
- Sbase = 30 MVA = 30 × 106 VA
- Vbase = 13.2 kV = 13.2 × 103 V
Substituting the values:
Ibase = (30 × 106) / (√3 × 13.2 × 103)
Ibase = 1311.78 A
So, the base current of the system is 1311.78 A.
Step 2: Determine the per unit fault current for a line-to-ground fault
In the case of a line-to-ground fault, the equivalent impedance is given by:
ZLG = Z1 + Z2 + (Z0 || ZN)
Where:
- Z1 = Positive sequence impedance = 0.30 pu
- Z2 = Negative sequence impedance = 0.40 pu
- Z0 = Zero sequence impedance = 0.05 pu
- ZN = Neutral reactance to be determined
The fault current is inversely proportional to the equivalent impedance. The fault current in per unit (If) for a line-to-ground fault can be expressed as:
If = 1 / ZLG
We are tasked with limiting the fault current to the rated line current (i.e., 1 pu). Hence, the equivalent impedance must satisfy:
ZLG = 1 pu
Substituting the values into the equation for ZLG:
1 = 0.30 + 0.40 + (0.05 || ZN)
Step 3: Solve for ZN
The parallel combination of Z0 and ZN is given by:
(0.05 || ZN) = (Z0 × ZN) / (Z0 + ZN)
Substituting this into the equation for ZLG:
1 = 0.30 + 0.40 + [(0.05 × ZN) / (0.05 + ZN)]
Rearranging:
0.30 + 0.40 = 0.70
1 - 0.70 = (0.05 × ZN) / (0.05 + ZN)
0.30 = (0.05 × ZN) / (0.05 + ZN)
Cross-multiplying:
0.30 × (0.05 + ZN) = 0.05 × ZN
Expanding and simplifying:
0.015 + 0.30 × ZN = 0.05 × ZN
0.30 × ZN - 0.05 × ZN = 0.015
0.25 × ZN = 0.015
Solving for ZN:
ZN = 0.015 / 0.25 = 0.06 pu
Step 4: Convert ZN to ohms
To convert the per unit reactance into ohms, we use the base impedance:
Zbase = (Vbase)2 / Sbase
Substituting the values:
Zbase = (13.2 × 103)2 / (30 × 106)
Zbase = 5.808 ohms
Now, the neutral reactance in ohms is:
XN = ZN × Zbase
XN = 0.06 × 5.808
XN = 0.34848 ohms
**